Festo

CPX-AP Digital I/O Module - 4-Inputs/4-Outputs, M8 3-Pin

Part number CPX-AP-I-4DI4DO-M8-3P

Overview

Digital input/output module; Series: Individual devices for automation system CPX-AP-I; Output ducts: 4 output channels; Input channels: 4 input channels; Switching input/output: PNP; Function module: Digital inputs/outputs

Technical data

Dimensions (W x L x H) 30 x 170 x 35 mm
Type of mounting On H-rail via accessories, With through-hole
Product weight 129 g
Ambient temperature -20 – 60°C
Storage temperature -40 – 70°C
Relative air humidity 5 - 95%, Non-condensing
Degree of protection IP65, IP67
Note on degree of protection Unused connections sealed
Corrosion resistance class CRC 1 - Low corrosion stress
Max. cable length 30 m outputs, 30 m inputs, 50 m system communication
Note on max. cable length Power supply according to nominal voltage
LABS (PWIS) conformity VDMA24364-B2-L
Cleanroom suitability, measured according to ISO 14644-14 Element installed statically, no meaningful evaluation possible according to ISO 14644-1
CE mark (see declaration of conformity) To EU EMC Directive
UKCA marking (see declaration of conformity) To UK instructions for EMC
KC mark KC-EMV
Approval RCM trademark, c UL us listed (OL)
Certificate issuing authority UL E239998
Note on materials RoHS-compliant
Material housing PA, PC, Die-cast zinc, nickel-plated
Material o-ring FPM
Diagnostics via LED Diagnostics per module, Load power supply, Status per channel
Diagnostics per internal communication Load switch-off, Short-circuit/overload in output signal, Short circuit/overload in sensor supply, Electronics/sensors overvoltage, Load overvoltage, Electronics/sensors undervoltage, Load undervoltage
Number of outputs 4
Communication interface, function System communication XF10 IN / XF20 OUT
Communication interface, connection type 2x socket
Communication interface, connection technology M8x1, D-coded according to EN 61076-2-114
Communication interface, number of pins/cores 4
Communication interface, protocol AP
Communication interface, screened yes
Power supply, function Incoming electronics/sensors and load
Power supply, connection type Plugs
power supply, connection system M8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires 4
Power transmission, function Outgoing electronics/sensors and load
Power transmission, connection type Socket
Power transmission, connection technology M8x1, A-coded to EN 61076-2-104
Power transmission, number of pins/wires 4
Note regarding operating voltage SELV/PELV fixed power supplies required, Note voltage drop
Nominal operating voltage DC of load 24 V
Permissible voltage fluctuation of load ± 25 %
Nominal DC operating voltage, electronics/sensors 24 V
Permissible voltage fluctuations for electronics/sensors ± 25%
Max. power supply 2 x 4 A (external fuse required)
Intrinsic current consumption at nominal operating voltage for electronics/sensors Typically 35 mA
Intrinsic current consumption at nominal operating voltage load Typically 10 mA
Power failure bridging 10 ms
Reverse polarity protection yes
Electrical connection input, function Digital input
Electrical connection input, connection type 4x socket
Electrical connection input, connector system M8x1, A-coded to EN 61076-2-104
Electrical connection input, number of connections/cores 3
Number of inputs 4
Characteristic for inputs To IEC 61131-2, type 3
Switching level Signal 0: <= 5 V, Signal 1: >= 11 V
Switching logic for inputs PNP (positive switching), 2-wire sensors to IEC 61131-2, 3-wire sensors to IEC 61131-2
Input debounce time 0.1 ms, 3 ms, 10 ms, 20 ms
Fuse protection of inputs (short circuit) Internal electronic fuse per module
Max. residual current of inputs per module 1.8 A
Electrical isolation of inputs between channels no
Electrical isolation of inputs between channel – internal communication yes
Electrical connection output, function Digital output
Electrical connection output, connection type 4x socket
Electrical connection output, connector system M8x1, A-coded to EN 61076-2-104
Electrical connection output, number of connections/cores 3
Characteristic for outputs According to IEC 61131-2, type 0.5
Switching logic for outputs PNP (positive switching)
Fuse protection of outputs (short circuit) Internal electronic fuse per channel
Output delay with ohmic load Signal change 0->1: < 200 µs, Signal change 1->0: < 200 µs
Max. residual current outputs per module 2 A
Electrical isolation of outputs between channels no
Electrical isolation of outputs between channel - internal communication yes
Max. power supply per channel 0.5 A

Often bought with