EtherNet/IP interface; Series: Individual devices for automation system CPX-AP-I; Input channels: None; Function module: Fieldbus connection
Technical data
| Dimensions (W x L x H) | 45 x 170 x 35 mm |
|---|---|
| Type of mounting | On H-rail via accessories, With through-hole |
| Max. number of modules | 80 |
| Product weight | 194 g |
| Ambient temperature | -20 – 60°C |
| Storage temperature | -40 – 70°C |
| Relative air humidity | 5 - 95%, Non-condensing |
| Degree of protection | IP65, IP67 |
| Note on degree of protection | Unused connections sealed |
| Corrosion resistance class CRC | 1 - Low corrosion stress |
| Max. cable length | 50 m system communication |
| Note on max. cable length | Power supply according to nominal voltage |
| LABS (PWIS) conformity | VDMA24364-B2-L |
| Cleanroom suitability, measured according to ISO 14644-14 | Element installed statically, no meaningful evaluation possible according to ISO 14644-1 |
| CE mark (see declaration of conformity) | To EU EMC Directive |
| UKCA marking (see declaration of conformity) | To UK instructions for EMC |
| KC mark | KC-EMV |
| Approval | RCM trademark, c UL us listed (OL) |
| Certificate issuing authority | UL E239998 |
| Note on materials | RoHS-compliant |
| Material housing | PA, PC, Die-cast zinc, nickel-plated |
| Material o-ring | FPM |
| Diagnostics via LED | Diagnostics per module, Network status Ethernet/IP, Power supply, electronics/sensors, Load power supply, System diagnostics, Service required |
| Diagnostics via bus | APDD invalid, Load switch-off, Communication with AP module interrupted, Electronics/sensors overvoltage, Load overvoltage, Electronics/sensors undervoltage, Load undervoltage |
| Diagnostics per internal communication | Module error, Output short circuit/overload, Short circuit/overload in sensor supply, Undervoltage in load supply |
| Fieldbus interface | Ethernet |
| Field bus, protocol | EtherNet/IP |
| Fieldbus interface, function | Bus connection incoming/outgoing |
| Field bus, connection type | 2x socket |
| Field bus, connection system | M12x1, D-coded to EN 61076-2-101 |
| Field bus, connection pattern | 4 |
| Field bus interface, electrical isolation | yes |
| Field bus interface, transmission rate | 100 Mbit/s |
| Max. address volume, inputs | 1324 |
| Max. address volume, outputs | 1324 |
| Configuration support | EDS file |
| Communication interface, function | System communication XF20 OUT / XF21 OUT |
| Communication interface, connection type | 2x socket |
| Communication interface, connection technology | M8x1, D-coded according to EN 61076-2-114 |
| Communication interface, number of pins/cores | 4 |
| Communication interface, protocol | AP |
| Communication interface, screened | yes |
| Power supply, function | Incoming electronics/sensors and load |
| Power supply, connection type | Plugs |
| power supply, connection system | M8x1, A-coded to EN 61076-2-104 |
| Power supply, number of pins/wires | 4 |
| Power transmission, function | Outgoing electronics/sensors and load |
| Power transmission, connection type | Socket |
| Power transmission, connection technology | M8x1, A-coded to EN 61076-2-104 |
| Power transmission, number of pins/wires | 4 |
| Note regarding operating voltage | SELV/PELV fixed power supplies required, Note voltage drop |
| Nominal operating voltage DC of load | 24 V |
| Permissible voltage fluctuation of load | ± 25 % |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ± 25% |
| Max. power supply | 2 x 4 A (external fuse required) |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 90 mA |
| Intrinsic current consumption at nominal operating voltage load | Typically 5 mA |
| Power failure bridging | 10 ms |
| Reverse polarity protection | yes |