Festo
CPX-E Counter Module - 4 inputs
Part number CPX-E-1CI
Overview
Counter module CPX-E-1CI Counter module CPX-E-1CI Series: Individual component for automation system CPX-E; Input channels: 1 input channel; Switching input/output: Counter module
Technical data
| Dimensions (W x L x H) | 18.9 x 76.6 x 124.3 mm |
|---|---|
| Grid dimension | 18.9 mm |
| Type of mounting | With H-rail |
| Product weight | 88 g |
| Mounting position | Vertical, Horizontal |
| Ambient temperature | -5 – 50°C |
| Note on ambient temperature | -5 - 60°C for vertical installation |
| Storage temperature | -20 – 70°C |
| Relative air humidity | 95 %, Non-condensing |
| Degree of protection | IP20 |
| Corrosion resistance class CRC | 0 - No corrosion stress |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| LABS (PWIS) conformity | VDMA24364 zone III |
| CE mark (see declaration of conformity) | To EU EMC Directive, In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK instructions for EMC, To UK RoHS instructions |
| KC mark | KC-EMV |
| Approval | RCM trademark, c UL us listed (OL) |
| Certificate issuing authority | UL E239998 |
| Note on materials | RoHS-compliant |
| Material housing | PA |
| Material screws | Galvanised steel |
| Diagnostics via LED | Encoder supply error, Errors per module, Encoder error, Encoder normal operation, Encoder supply normal operation, Status per channel |
| Diagnostics via bus | Measuring system error, Short circuit/overload in sensor supply, Parameter errors, Monitoring of wire break, Monitoring of zero pulse, Tracking error monitoring |
| Max. address volume, inputs | 12 |
| Max. address volume, outputs | 2 |
| Module parameters | Debounce time for digital inputs, Pulse/zero pulse, Integration time for speed measurement, Internal revision ID, Load value, Latching event, Latching signal, Latching response, Upper count limit, Signal type/encoder type, Signal evaluation, Monitoring of cable break, Monitoring of zero pulse, Tracking error monitoring, Lower count limit |
| Channel parameters | Signal extension |
| Power supply, function | Encoder supply |
| Power supply, connection type | Terminal strip |
| power supply, connection system | Spring-loaded terminal |
| Power supply, connection pattern | 995844 |
| Power supply, number of pins/wires | 6 |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ± 25% |
| Power supply, conductor diameter | 0.2 – 1.5 |
| Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 15 mA |
| Power failure bridging | 10 ms |
| Reverse polarity protection | 24 V sensor supply against 0 V sensor supply |
| Electrical connection input, function | Digital input |
| Electrical connection input, connection type | 2x terminal strip |
| Electrical connection input, connector system | Spring-loaded terminal |
| Electrical connection input, number of connections/cores | 6 |
| Electrical connection input, connection pattern | 995843 |
| Electrical connection for input, conductor cross section | 0.2 – 1.5 |
| Electrical connection for input, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Electrical connection for input 2, function | Counting input |
| Electrical connection for input 2, connection type | Terminal strip |
| Electrical connection for input 2, connection technology | Spring-loaded terminal |
| Electrical connection for input 2, number of pins/wires | 6 |
| Electrical connection for input 2, connection pattern | 995848 |
| Electrical connection for input 2, conductor cross section | 0.2 – 1.5 |
| Electrical connection for input 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Number of inputs | 4 |
| Characteristic for inputs | To IEC 61131-2, type 3 |
| Switching level | Signal 0: <= 5 V, Signal 1: >= 11 V |
| Switching logic for inputs | PNP (positive switching), 2-wire sensors to IEC 61131-2, 3-wire sensors to IEC 61131-2 |
| Input debounce time | 0.02 ms, 0.1 ms, 3 ms |
| Behaviour after end of overload of the sensor supply | Automatic return |
| Max. residual current of inputs per module | 1.8 A |
| Isolation channel - channel | no |
| Isolation channel - internal bus | no |
| Fuse protection (short circuit) | Internal electronic fuse per module |
Similar products
Box Remote I/O Module B32-EC-11-26
CPX-AP 4-port IO-Link master 2 models
CPX-AP-I 4DI/4DO module 2 models
CPX-AP-I bus interface 4 models
CPX-AP-I digital input module 6 models
CPX-AP-I digital output module 2 models