Festo

CPX-CEC Control Block - 24 V, CODESYS Level 2, 95 %

Part number CPX-CEC-C1-V3

Overview

Control block CPX-CEC-C1-V3 Control block CPX-CEC-C1-V3 Series: Individual component for electrical terminal CPX

Technical data

Protocol CODESYS Level 2, EasyIP, Modbus® TCP, TCP/IP
Dimensions (W x L x H) 50 x 107 x 55 mm
Product weight 135 g
Ambient temperature -5 – 50°C
Storage temperature -20 – 70°C
Relative air humidity 95 %, Non-condensing
Degree of protection IP65, IP67
Corrosion resistance class CRC 2 - Moderate corrosion stress
LABS (PWIS) conformity VDMA24364-B2-L
Note on materials RoHS-compliant
Material housing PA-reinforced, PC
LED display, product-specific ERR: PLC runtime error, M: Modify/forcing active, PL: Load supply, PS: Electronics supply, sensor supply, RUN: PLC status, SF: System fault, STOP: PLC status
LED display, bus-specific TP: Link/traffic
Device-specific diagnostics Channel-oriented and module-oriented diagnostics, Undervoltage/short circuit of modules, Diagnostic memory
Operator controls DIL switch for CAN termination, Rotary switch for RUN/STOP
IP address setting DHCP, Via CODESYS, Via MMI
Fieldbus interface CAN bus
Field bus interface, connection system Plugs, Sub-D, 9-pin
Field bus interface, electrical isolation yes
Field bus interface, transmission rate 125, 250, 500, 800, 1000 kbit/s, Can be set using software
Ethernet interface RJ45 (socket, 8-pin)
Ethernet, number 1
Ethernet, supported protocols TCP/IP, EasyIP, Modbus TCP
Ethernet, plug connector RJ45, Bushing, 8-pin
Ethernet, data transmission rate 10/100 Mbit/s
Parameterisation CODESYS V3
Configuration support CODESYS V3
Additional functions Diagnostic functions, Motion functions for electric drives
CPU data 256 MB RAM, 32 MB flash, 800 MHz processor
Control-Interface CAN bus
Nominal operating voltage DC 24 V
Nominal DC operating voltage, load voltage Without pneumatic components: 18 ... 30 V, 24 V, With pneumatics type midi/maxi: 21.6 ... 26.4 V, With pneumatics type CPA: 20.4 ... 26.4 V, With pneumatics type MPA: 18 ... 30 V
Intern power consumption nominal operating voltage Typ. 85 mA
Power failure bridging 10 ms
Programming, operating language DE, EN
Programming language To IEC 61131-3, KOP, AWL, ST, FUP, AS, Additionally CFC
Programming, support for file handling yes
Programming software CODESYS provided by Festo
Program memory 16 MB user program
Processing time Approx. 200 µs/1 k instruction
Function modules Read CPX module diagnostics, CPX diagnostic status, Copy CPX diagnostic trace, And others
Flag 28 kB remanent data, CODESYS variable concept
Total number of axes 127