Festo

CPX-E Analogue Output Module - 4-Outputs

Part number CPX-E-4AO-U-I

Overview

Analogue output module; Series: Individual component for automation system CPX-E; Output ducts: 4 output channels; Input channels: None

Technical data

Dimensions (W x L x H) 18.9 x 76.6 x 124.3 mm
Grid dimension 18.9 mm
Type of mounting With H-rail
Product weight 96 g
Mounting position Vertical, Horizontal
Ambient temperature -5 – 50°C
Note on ambient temperature -5 - 60°C for vertical installation
Storage temperature -20 – 70°C
Relative air humidity 95 %, Non-condensing
Degree of protection IP20
Corrosion resistance class CRC 0 - No corrosion stress
Vibration resistance Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6
Shock resistance Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection against direct and indirect contact PELV
Max. cable length 30 m outputs, Shielded
LABS (PWIS) conformity VDMA24364 zone III
CE mark (see declaration of conformity) To EU EMC Directive, In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity) To UK instructions for EMC, To UK RoHS instructions
KC mark KC-EMV
Approval RCM trademark, c UL us listed (OL)
Certificate issuing authority UL E239998
Note on materials RoHS-compliant
Material housing PA
Material screws Galvanised steel
Diagnostics via LED Errors per channel, Errors per module
Diagnostics via bus Short circuit/overload in actuator supply, Short circuit/overload at analogue output, Parameterisation error, Nominal range exceeded, Nominal range not reached, Undervoltage in load supply, General errors
Max. address volume, outputs 8
Number of outputs 4
Module parameters Deactivate actuator supply, Data format for analogue outputs, Short circuit diagnostics for actuator supply, Parameterisation error diagnostics, Diagnostics for undervoltage in load supply, Behaviour after short circuit/overload in actuator supply, Behaviour after short circuit/overload at analogue output
Channel parameters Force channel x, Enable wire break/idling diagnostics, Enable for parameterisation error diagnostics, Enable overload/short circuit diagnostics, Signal range per channel
Power supply, connection type Terminal strip
power supply, connection system Spring-loaded terminal
Power supply, connection pattern 995847
Power supply, number of pins/wires 4
Nominal operating voltage DC of load 24 V
Permissible voltage fluctuation of load ± 25 %
Nominal DC operating voltage, electronics/sensors 24 V
Permissible voltage fluctuations for electronics/sensors ± 25%
Power supply, conductor diameter 0.2 – 1.5
Power supply, note on conductor diameter 0.2 - 2.5 mm² for flexible conductors without wire ferrule
Intrinsic current consumption at nominal operating voltage for electronics/sensors Typically 60 mA
Intrinsic current consumption at nominal operating voltage load Typically 15 mA
Power failure bridging 10 ms
Reverse polarity protection 24 V actuator supply against 0 V sensor supply, 24 V load against 0 V load, 24 V sensor supply against 0 V sensor supply
Electrical connection output, function Analogue output
Electrical connection output, connection type 4x terminal strip
Electrical connection output, connector system Spring-loaded terminal
Electrical connection output, number of connections/cores 4
Electrical connection output, connection pattern 995841
Electrical connection for output, conductor cross section 0.2 – 1.5
Electrical connection for output, note on conductor cross section 0.2 - 2.5 mm² for flexible conductors without wire ferrule
Electrical connection for output 2, function Functional earth
Electrical connection for output 2, connection type Terminal strip
Electrical connection for output 2, connection technology Spring-loaded terminal
Electrical connection output 2, number of pins/wires 4
Electrical connection output 2, connection pattern 995842
Electrical connection output 2, conductor cross section 0.2 – 1.5
Electrical connection output 2, note on conductor cross section 0.2 - 2.5 mm² for flexible conductors without wire ferrule
Behaviour after end of overload of the outputs No automatic return (default), Parameterisable (module by module)
Max. residual current outputs per module 2 A
Measured variable Voltage, Current
Data format 15 bits + prefix, Linear scaling
analog input -10 - 10 V, -5 - 5 V, 0 - 10 V, -20 - 20 mA, 0 - 20 mA, 4 - 20 mA
Repetition accuracy ±0.05% at 25°C
Basic error limit at 25 °C ±0.1%
Operating error limit related to the ambient temperature range ±0.3%
Isolation channel - channel no
Isolation channel - internal bus yes
Fuse protection (short circuit) Internal electronic fuse per module