Overview
Analogue output module; Series: Individual component for automation system CPX-E; Output ducts: 4 output channels; Input channels: None
Technical data
| Dimensions (W x L x H) | 18.9 x 76.6 x 124.3 mm |
|---|---|
| Grid dimension | 18.9 mm |
| Type of mounting | With H-rail |
| Product weight | 96 g |
| Mounting position | Vertical, Horizontal |
| Ambient temperature | -5 – 50°C |
| Note on ambient temperature | -5 - 60°C for vertical installation |
| Storage temperature | -20 – 70°C |
| Relative air humidity | 95 %, Non-condensing |
| Degree of protection | IP20 |
| Corrosion resistance class CRC | 0 - No corrosion stress |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Protection against direct and indirect contact | PELV |
| Max. cable length | 30 m outputs, Shielded |
| LABS (PWIS) conformity | VDMA24364 zone III |
| CE mark (see declaration of conformity) | To EU EMC Directive, In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK instructions for EMC, To UK RoHS instructions |
| KC mark | KC-EMV |
| Approval | RCM trademark, c UL us listed (OL) |
| Certificate issuing authority | UL E239998 |
| Note on materials | RoHS-compliant |
| Material housing | PA |
| Material screws | Galvanised steel |
| Diagnostics via LED | Errors per channel, Errors per module |
| Diagnostics via bus | Short circuit/overload in actuator supply, Short circuit/overload at analogue output, Parameterisation error, Nominal range exceeded, Nominal range not reached, Undervoltage in load supply, General errors |
| Max. address volume, outputs | 8 |
| Number of outputs | 4 |
| Module parameters | Deactivate actuator supply, Data format for analogue outputs, Short circuit diagnostics for actuator supply, Parameterisation error diagnostics, Diagnostics for undervoltage in load supply, Behaviour after short circuit/overload in actuator supply, Behaviour after short circuit/overload at analogue output |
| Channel parameters | Force channel x, Enable wire break/idling diagnostics, Enable for parameterisation error diagnostics, Enable overload/short circuit diagnostics, Signal range per channel |
| Power supply, connection type | Terminal strip |
| power supply, connection system | Spring-loaded terminal |
| Power supply, connection pattern | 995847 |
| Power supply, number of pins/wires | 4 |
| Nominal operating voltage DC of load | 24 V |
| Permissible voltage fluctuation of load | ± 25 % |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ± 25% |
| Power supply, conductor diameter | 0.2 – 1.5 |
| Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 60 mA |
| Intrinsic current consumption at nominal operating voltage load | Typically 15 mA |
| Power failure bridging | 10 ms |
| Reverse polarity protection | 24 V actuator supply against 0 V sensor supply, 24 V load against 0 V load, 24 V sensor supply against 0 V sensor supply |
| Electrical connection output, function | Analogue output |
| Electrical connection output, connection type | 4x terminal strip |
| Electrical connection output, connector system | Spring-loaded terminal |
| Electrical connection output, number of connections/cores | 4 |
| Electrical connection output, connection pattern | 995841 |
| Electrical connection for output, conductor cross section | 0.2 – 1.5 |
| Electrical connection for output, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Electrical connection for output 2, function | Functional earth |
| Electrical connection for output 2, connection type | Terminal strip |
| Electrical connection for output 2, connection technology | Spring-loaded terminal |
| Electrical connection output 2, number of pins/wires | 4 |
| Electrical connection output 2, connection pattern | 995842 |
| Electrical connection output 2, conductor cross section | 0.2 – 1.5 |
| Electrical connection output 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Behaviour after end of overload of the outputs | No automatic return (default), Parameterisable (module by module) |
| Max. residual current outputs per module | 2 A |
| Measured variable | Voltage, Current |
| Data format | 15 bits + prefix, Linear scaling |
| analog input | -10 - 10 V, -5 - 5 V, 0 - 10 V, -20 - 20 mA, 0 - 20 mA, 4 - 20 mA |
| Repetition accuracy | ±0.05% at 25°C |
| Basic error limit at 25 °C | ±0.1% |
| Operating error limit related to the ambient temperature range | ±0.3% |
| Isolation channel - channel | no |
| Isolation channel - internal bus | yes |
| Fuse protection (short circuit) | Internal electronic fuse per module |
Similar products
Box Remote I/O Module B32-EC-11-26
CPX-AP Bus Interface - EtherCAT CPX-AP-I-EC-M12
CPX-AP Bus Interface - EtherNet/IP CPX-AP-I-EP-M12
CPX-AP Digital I/O Module - 4-Inputs/4-Outputs, M8 3-Pin CPX-AP-I-4DI4DO-M8-3P
CPX-AP IO-Link Master Module - 4-Ports CPX-AP-I-4IOL-M12
CPX-AP Digital Input Module - 8-Inputs, M8 3-Pin CPX-AP-I-8DI-M8-3P